16 Channel Input/Output Board FN-4127-IO
DESCRIPTION:
- 16 channels of input/output points.
- 32 I/O boards per FireNET panel (512 channels of input/output points).
- Each channel configurable as input or output point.
- Inputs are opto-isolated non-supervised pulldown type triggered.
- Outputs are open collector transistor pulldown type (100mA max each).
- Simple 4 wire connection to control panel (2 for power, 2 for data).
- All inputs/outputs can be assigned to global functions, any event category, and used in network wide.
- Cause & Effect logic.
- Can be mounted locally within control panel enclosure or remotely via FN-ACC accessory enclosure up to 4000ft from the panel.
- Each I/O board has a unique address 1-32 (set via DIP switch) on the I/O.
- Comms Bus Input/Outputs are for secondary use, not for primary fire initiation inputs or notification outputs.
- Two LED's are provided for communication status