Manufacturers: Horing Lih
Origin: Taiwan
Characteristics
The AH-0822 features advanced technology, high accurate detection, low power-consumption and fast reaction time. It can detect natural gas and propane gas. Built-in buzzer and LED indicator alert by sounding and flashing.
Sounding and flashing in alarm status; the green LED is lit during monitoring and the red LED flashes in alarm status.
Dual power input: 12VDC and 24VDC operation in the same unit. No adjustment is required.
Optional 110VAC or 220VAC adaptor is available.
1 set of relay output: COM. NO. NC. for CE version.
Approval
Specifications
Model |
AH-0822 |
|||
Approval |
UL |
CE |
||
Power Source |
24V DC |
12V DC |
24V DC |
12V DC |
Standby Current |
25~30mA |
40~45mA |
35~40mA |
65~70mA |
Alarm Current |
40~70mA |
50~75mA |
75~90mA |
90~105mA |
Warm-up Period |
5~8 minutes |
about 35 seconds |
||
Sensitivity |
0.021 ~ 0.300% (Propane) 0.050 ~ 0.714% (Methane) |
0.050 ~ 0.300% |
||
Alarm Sound |
85dB/3M and above |
90dB/M and above |
||
Detection Type |
Natural Gas & Propane Gas |
|||
Ambient Temperature |
-10°C ~ +55°C |
|||
Dimensions |
102 mm (Dia.) x 40.5 mm(H) |
|||
Weight |
About 130g |
Download