Manufacturers: GST
Origin: China
DI-9319E Digital Zone Monitor Unit is designed to connect conventional detectors into addressable system. When any device reports fire signal, the module will transmit the signal to the fire alarm control panel which generates fire alarm and displays the address of the module. It is also suitable to connect dry contacts input, collect action or fault signals.
Feature
☆Input port cable monitoring with 4.7KΩ EOLR
☆Monitoring power supply.
☆Two indicators for fire and fault.
☆Normally-open or Normally-close output automatically follows input port to change state
☆Electronically addressed. Addresses can be modified in field.
☆LED status indication
☆Din-Rail mount or surface mount
☆Standard: EN 54-18:2005
☆LPCB Approved
Technical Specifications
☆Operating Voltage: Loop 24VDC (16VDC - 28VDC) Power Limited
☆ Standby Current:
Loop≤ 0.38mA
Power≤ 10mA
☆ Action Current:
Loop≤ 0.39mA
Power≤ 60mA
☆Output Capacity: 2A@30VDC
☆Input Capacity: Up to 30 conventional detectors
☆ Operating Environment:
Temperature: -10℃ - +55℃
Relative Humidity≤ 95%, non-condensing
☆ Dimension: 85.3mm×78.0mm×33.0mm